Monchrui

MONCHRUI . Your reliable HVAC partner!

Description

Horizontal Split Case Pump Vertical Split Case Centrifugal Pump (Horizontal & Vertical Split Case Pump)

Horizontal Split Case Pump Vertical Split Case Centrifugal Pump

Horizontal & Vertical Split Case Double Suction Centrifugal Pump Large Flow Pump For Municipal & District Heating

1. Product Overview

Horizontal split case pump & vertical split case pump are single/two-stage double suction double volute large-flow centrifugal pumps with axially split casing. The core merit is that maintenance can be done without removing pipes or motor. Hydraulic components optimized via CFD simulation with wide high-efficiency operating range, low rated NPSHr 2~5m for excellent anti-cavitation performance. Max flow up to 15000m³/h, max head 250m, liquid temperature 0~120℃, max working pressure 25bar, motor power 1.1~2240kW. Five standard factory assembly types available. Standard cast iron casing with stainless impeller, ductile iron & duplex stainless customized for corrosive water. Widely applied in municipal water, district energy, commercial HVAC, agricultural irrigation, desalination & industrial cooling.

Comparison: Horizontal VS Vertical Split Case Pump

Comparison Item

Horizontal Split Case Pump

Vertical Split Case Pump

Mounting Structure

Horizontal base, long coupled motor

Vertical floor-mounted, save floor space

Inlet & Outlet Layout

Horizontal inline straight

Horizontal ports, vertical pump body

Suitable Machine Room

Spacious new water plant with high ceiling

Narrow retrofitted plant with limited height

Main Assembly Types

Complete set with base, split base unit

Bare pump with base, base-free customized

Vibration Performance

Damped base, stable running

Vertical force, smaller radial vibration

Typical Application

Municipal water plant, district heating main pump

Mall HVAC, park secondary circulation pump

General Technical Specifications

Category

Item

Standard Parameter

Hydraulic Performance

Pump Structure

Single / Two-stage double suction double volute centrifugal pump

Max Flow Rate

15000 m³/h

Max Head

250 m

Rated NPSHr

2 ~ 5 m

Liquid Temp Range

0 ~ 120 ℃

Max Working Pressure

25 bar

Motor Power Range

1.1 ~ 2240 kW

Hydraulic Design

CFD optimized impeller, high efficiency within ±20% flow deviation

Mechanical Structure

Casing Type

Axial split top & bottom casing

Standard Material

Cast iron casing, stainless steel impeller

Custom Material

Ductile iron, duplex stainless steel casing & impeller

Shaft Seal Options

Mechanical seal, graphite packing seal

Compliance Standard

ISO5199; impeller dynamic balance ISO1940 G6.3

Flange Standard

DIN EN1092

Five Standard Factory Assembly Versions

Assembly Type

Configuration Description

Suitable Projects

Complete unit with standard base

Pump + motor + integrated base full set

New standard water plant construction

Bare pump with base

Pump only without motor, matched base supplied

Customer self-provide high-power motor

Base-free bare pump

Pump body only, no base & motor

Replacement on existing foundation

Split base complete unit

Separate pump & motor base

Heavy high-power unit vibration reduction

Split base bare pump

Bare pump with separated base

Non-standard plant foundation customization

2 Eight Core Product Advantages

  1. Axially Split Casing, No Pipe Disassembly For Maintenance Top-bottom split design, inspect impeller, seal & bearing after opening top cover; no need to detach flanges or move motor, greatly shorten downtime for municipal water plant overhaul.

  2. Double Suction & Double Volute Low Vibration Long Service Life Dual inlet balance axial thrust; double volute counteracts radial force, reduce wear of bearing & seal by 60%, bearing rated life up to 50,000 hours.

  3. Wide Range High Hydraulic Efficiency CFD full flow simulation, keep high efficiency even when flow deviates ±20% from rated point, save power for parallel pump stations & variable flow district energy plants.

  4. Ultra Low NPSHr 2~5m, Stable For Surface Water Intake Low cavitation risk for reservoir & river intake pumps, no impeller pitting damage under long-term continuous operation.

  5. Horizontal & Vertical Dual Models Fit All Plant Conditions LS horizontal for spacious new waterworks; LSV vertical save floor space, ideal for narrow old HVAC room renovation.

  6. Custom Anti-Corrosion Materials For Fresh & Seawater Standard cast iron for tap water; ductile iron for industrial softened water; duplex stainless steel for desalination & mildly corrosive liquid. 7 Five Assembly Options Match All Supporting Demands Complete unit, bare pump, split base for new construction, retrofit & customer self-motor projects. 8 Full Power Coverage For Heavy Large-Flow Conditions 1.1kW small circulation up to 2240kW main water plant pump, meet ten-thousand-ton water supply & large district heating station demand.

3 Six Main Application Scenarios

1 Municipal Water Supply: Urban waterworks, reservoir surface intake pump stations;

2 District Energy Plants: Primary & secondary circulation pumps for heating & cooling;

3 Commercial HVAC: Large shopping mall, exhibition & hotel chilled water main circulation;

4 Agricultural Water Conservancy: Farmland irrigation & river diversion booster system;

5 Water Treatment: Desalination, large swimming pool circulation, industrial process cooling pump;

6 Industrial Supporting: Chemical park recirculating water, factory cooling supply.

4 Standard Installation & Maintenance Guide

1 Piping: Install rubber flexible joints at inlet & outlet, keep straight pipe ≥8 times diameter before & after pump;

2 Foundation: Concrete damping base for complete unit, extra vibration pad for high-power models;

3 Seal Selection: Mechanical seal for clean water, packing seal for liquid with sediment;

4 Filtration: Large-flow Y strainer installed at suction side to protect impeller from sand;

5 Maintenance: Open split casing to inspect wear ring & seal regularly, replace bearing grease every 2 years.

Contact Us